Cable Size and Voltage Drop Calculator

Calculate the voltage drop on a circuit from generator to panel or from panel to load, and see the minimum cable size that keeps within your limit.

Enter the circuit details

Method

How is it calculated?

The calculation uses the common voltage drop relation:

3-phase: %e = 100 × P × L ÷ (k × S × V²)  |  1-phase: %e = 200 × P × L ÷ (k × S × V²)

P: power (W), L: one-way length (m), S: cross-section (mm²), V: voltage, k: conductivity (copper 56, aluminium 35 m/Ω·mm² at 20 °C). As cables heat up under load, the 70 °C option uses k = 47 for copper and 29 for aluminium, which gives a safer result.

Cable reactance is neglected; on large sizes and long runs the real drop can be slightly higher. Besides voltage drop, the size must also be checked for current-carrying capacity, short-circuit withstand and the protective device.

Frequently asked questions

What voltage drop is acceptable?

The limit depends on the installation type and the rules that apply. 3% for power circuits and lower values for lighting are common; use the limit in your design.

How is the generator-to-panel cable selected?

Rated current, run length, installation method and fault level are considered together. Voltage drop governs long runs; current-carrying capacity governs short, high-current runs.

Can aluminium cable be used?

Yes. Aluminium has about 62% of copper's conductivity, so a larger size is needed for the same drop. Terminations need suitable lugs and maintenance.

Does this check current-carrying capacity?

No. This tool calculates voltage drop only. Current-carrying capacity depends on installation method, grouping and ambient temperature and must be checked separately.