How is it calculated?
The calculation uses the common voltage drop relation:
3-phase: %e = 100 × P × L ÷ (k × S × V²) | 1-phase: %e = 200 × P × L ÷ (k × S × V²)
P: power (W), L: one-way length (m), S: cross-section (mm²), V: voltage, k: conductivity (copper 56, aluminium 35 m/Ω·mm² at 20 °C). As cables heat up under load, the 70 °C option uses k = 47 for copper and 29 for aluminium, which gives a safer result.
Cable reactance is neglected; on large sizes and long runs the real drop can be slightly higher. Besides voltage drop, the size must also be checked for current-carrying capacity, short-circuit withstand and the protective device.