How is it calculated?
Qc = P × (tan φ₁ − tan φ₂)
P: active power (kW), φ₁: present, φ₂: target power factor angle. Example: 200 kW, power factor 0.78 → 0.95 gives Qc = 200 × (0.802 − 0.329) ≈ 95 kVAr.
Running on a generator: if capacitor banks stay connected while the site runs on a generator, the power factor can turn leading at low load and upset the generator's voltage control. The correction panel should switch out or limit its steps on transfer to generator. Sites with many drives or UPS systems need detuned (reactor) power factor correction.